Central Heating boiler room from hell!
« on: May 28, 2012, 02:23:04 PM »
I just had to share this one.

Got called to this job a few days ago to find what I would in simple terms call criminal! A central heating system installed about 7 years ago and signed off by council. To the left there (not very clear) are 2 x 50KW gas boilers supplying heat to system that provides hot water and radiant heat to a 150 room complex. Here some brief system specifications:

  • The central Heating is open into the domestic so the water that you are heating the rooms with (steel rads!) is the same water you shower and drink
  • No munzen rings, here its all hanging off 5mm wire and the list goes on.

All circulation pumps are leaking and the storage tank that you see is the first in line supposedly to pump into a second one to provide a large storage capacity, this doesn't work correctly due to the design of the pipework and is resulting in the boilers heating water that is never used. The expansion vessel drain is a 15mm dux pipe (I doubt that the expansion vessel has been sized correctly).

The first thing that hit me is the smell of gas when I opened the door. NO ventilation, good think im not a smoker, imagine walking into that thing with a cigi. The things you sometimes find  :o



Linkback: https://www.plumbers.nz/central-heating-and-underfloor-heating/8/central-heating-boiler-room-from-hell/1132/
Please note that the advice I am giving is only my opinion and not necessarily a fact.  Please refer to our terms and conditions.

Offline integrated

  • Sr. Member
  • ****
  • Posts: 412
  • Karma: +37/-2
Re: Central Heating boiler room from hell!
« Reply #1 on: May 28, 2012, 05:57:14 PM »
holy shiite!!

is it even certed?

Offline Plumber

  • Administrator
  • Hero Member
  • *****
  • Posts: 736
  • Karma: +52/-2
  • ***#1 Plumber***
Re: Central Heating boiler room from hell!
« Reply #2 on: May 28, 2012, 06:58:40 PM »
Apparently it is, im trying to get more info on this.

Offline Rodza1

  • Sr. Member
  • ****
  • Posts: 281
  • Karma: +20/-2
Re: Central Heating boiler room from hell!
« Reply #3 on: May 28, 2012, 07:59:11 PM »
thats unreal, probably some plumber/gasfitter out there who is proud of this installation too lol    ???     :o
The Plumbers Gasfitters And Drainlayers Board- "White Collar Mafia"

Offline o2b007

  • Jr. Member
  • **
  • Posts: 77
  • Karma: +6/-0
  • time for change!!
Re: Central Heating boiler room from hell!
« Reply #4 on: May 29, 2012, 07:21:27 AM »
I like how they have used fire line gib but no plastering or collars on the pipes....
It was proberbly a fly by night mechanical company that threw that togeather.

Offline Sophia Castella

  • Newbie
  • *
  • Posts: 1
  • Karma: +0/-0
Re: Central Heating boiler room from hell!
« Reply #5 on: July 08, 2014, 10:30:59 PM »
I think this post is really interesting and contained  great information about gas heating. :)

Offline methaneman

  • Newbie
  • *
  • Posts: 1
  • Karma: +0/-0
  • Im new @ Plumbers NZ!
Re: Central Heating boiler room from hell!
« Reply #6 on: November 24, 2014, 05:56:26 PM »
Hi new to here. Interesting pics, just a couple of things, boiler looks like a procon with that blue diagonal strip, if it is. this unit is room sealed? if so it shouldn't need full on ventilation, just ventilation for appliance cooling( which to be fair wouldn't get that hot)
other thing you mention is the plumbing crossed with heating, I doubt youd get the boiler to run if this was so, these units have a safety relief of 2.5 bar! and won't start, they are very temperamental german units jus like german cars!! , does this place have maintenance personell? maybe someone been tutuing with it?
Just a thought


Share via digg Share via facebook Share via linkedin Share via twitter

Similar Topics

  Subject / Started by Replies / Views Last post
xx
Gas Central Heating

Started by boltlass

2 Replies
4391 Views
Last post August 21, 2011, 12:20:03 AM
by heating55
xx
Central Heating Work

Started by robbo

2 Replies
4487 Views
Last post November 20, 2010, 05:44:19 PM
by robbo
question
legionnaire's risk - Central Heating

Started by Badger

19 Replies
6597 Views
Last post May 27, 2014, 09:30:24 PM
by Badger
clip
Smoko Room

Started by robbo

3 Replies
1869 Views
Last post May 20, 2014, 02:19:14 PM
by craftsman
 
Share this topic...
In a forum
(BBCode)
In a site/blog
(HTML)